3-3 Explicit Messaging
3-27
3
Communicating with the FD-MH series
- DeviceNet Compatible Network Unit DL-DN1 Users Manual (FD-MH) -
Nx10+2
6B
Instantaneous flow rate
setting 3 (P3)
*7 R/W
FD-MH10A
13.00
00.00 to 30.00
FD-MH50A
065.0
000.0 to 100.0
FD-MH100A
130.0
000.0 to 200.0
FD-MH500A
400.0
000.0 to 999.9
6C
Instantaneous flow rate
setting 4 (P4)
*7 R/W
FD-MH10A
20.00
00.00 to 30.00
FD-MH50A
100.0
000.0 to 100.0
FD-MH100A
200.0
000.0 to 200.0
FD-MH500A
500.0
000.0 to 999.9
6D to
83
System reserved
Nx10+3
64
Group-3 entry count
R-5
65
Key lock function
R/W - 0
0: Deactivate key lock
1: Key lock
66
System reserved
67
Analog output selection
*10 R/W - 0
0: Standard
1: Free range analog
68
Free range analog
upper limit
*10 R/W
FD-MH10A
10.0
0.0 to 30.00 (Settable unit: 0.1)
FD-MH50A
050
000 to 100 (Settable unit: 5)
FD-MH100A
100
000 to 200 (Settable unit: 10)
FD-MH500A
0500
0000 to 1000 (Settable unit: 50)
69
Free range analog lower
limit
*10 R/W
FD-MH10A
0.0
0.0 to 30.00 (Settable unit: 0.1)
FD-MH50A
000
000 to 100 (Settable unit: 5)
FD-MH100A
000
000 to 200 (Settable unit: 10)
FD-MH500A
0000
0000 to 1000 (Settable unit: 50)
6A to
83
System reserved
Nx10+4
64
Group-4 entry count
R-29
65
System reserved
66
Detection mode
R/W - 0
0: F-1
1: F-2
2: F-3
3: A-1
4: A-2
67
System reserved
68
Response time
R/W - 3
0: 0.05 s
1: 0.1 s
2: 0.5 s
3: 1.0 s
4: 2.5 s
5: 5.0 s
6: 10.0 s
7: 30.0 s
8: 60.0 s
69
Average display
*11 R/W - 1.0
00.0 to 10.0 (in steps of 0.5)
6A
Time-out time for
output 2
R/W - 10
1-99
6B
Integration direction
R/W - 0
0: Increment
1: Decrement
InstID
(DEC)
AttrID
(HEX)
Name
Description
Attribute
Sensor
head
Default
value
Parameter range