4
ADJUSTMENT
Measurement mode
Press the button
for 3 seconds or
more.
Press the button
once.
▲
■ Preset Value Input Mode
Determine the preset values.
● Auto-tuning mode (F-1)
1. In measurement mode with the
current measured value dis-
played, press . The AP-40A
enters the preset value input
mode.
2. “A” and the current preset value
flash alternately.
3. Position the target at the desired
upper (lower) limit.
4. Press
to register the value.
The updated value is displayed
for 1 second.
5. “b” and the current preset value
flash alternately.
6. Position the target at the desired
lower (upper) limit.
7. Press
to register the value. The updated value is displayed for 1
second.
8. “C” and the calculated preset value C flash alternately. (You can
change the C value to any value between A and b using
or
.)
9. Press to register the C value. The setting procedure is com-
pleted and the unit returns to measurement mode.
* To confirm the preset value, press repeatedly.
• Example of auto-tuning mode setting: Confirmation of work
piece pick-up.
Set the upper limit (A) to the position where the work piece is taken.
Set the lower limit (b) to the position where the nozzle becomes open
after releasing the work piece. Press
to register the upper and
lower limit values. The C value is automatically set to the midpoint
between the upper and lower limit values.
■ Hysteresis Mode (F-2), 2-independent Output
Mode (F-3), Window Mode (F-4)
1. In measurement mode with the
current measured value displayed,
press . The AP-40A enters the
preset value input mode.
2. “H”
1.
and the current preset value
flash alternately.
3. Use
or
to change the value
to the desired value. Press to
register the updated H value.
4. “h”
2.
and the current preset value
flash alternately.
5. Use
or
to change the value
to the desired value. Press to
register the updated h value.
6. “P”
3.
and the shift value of the
zero-shift adjustment flash
alternately.
8. Press to complete the setting procedure and return to measure-
ment mode.
* To confirm the preset value, press repeatedly.
❋ ❋ ❋ ❋
❋ ❋ ❋ ❋
❋ ❋ ❋ ❋
❋ ❋ ❋ ❋
❋ ❋ ❋ ❋
❋ ❋ ❋ ❋
• • •
• • •
• • •
• • •
A
A
(Measurement mode)
Current value
Flashes
alternately
Flashes
alternately
Flashes
alternately
Current upper
(lower) limit
value A
Current upper
(lower) limit
value b
The set value
C displays.
(C=
A + b
2
)
The updated value displays for 1 sec.
The updated value displays for 1 sec.
❋ ❋ ❋ ❋
❋ ❋ ❋ ❋
❋ ❋ ❋ ❋
• • •
• • •
1.
2.
3.
(Measurement mode)
Flashes
alternately
Current value
Flashes
alternately
Set the desired value
using
or
❋ ❋ ❋ ❋
Flashes
alternately
Set the desired value
using
or
• • •
[Example: In hysteresis mode]
1. “A” appears in the 2-independent
output mode.
2. “b” appears in the 2-independent
output mode.
“L” appears in the window mode.
3. Shown with RA/ZA type only.
* The setting is saved
in the EEPROM.
▲
▲
▲
Press the button once.
Note 1: When the operation mode is changed, check the preset values
in the preset value input mode.
Note 2: Perform the zero-shift adjustment periodically.
Note 3: The initial output voltage may fluctuate by ±1.0% immediately
after the power is turned on. To measure minute differences in
pressure, let the sensor warm up for approximately 15 to 30 minutes.
Note 4: The amount of zero shift ("P") is displayed without multiplica-
tion even in the zero-shift focus mode.
■ Operation Mode
Determine the desired operation mode.
(➮ Refer to “OPERATION MODE SELECTION” on page 3.)
The current operation mode is displayed. Use
or
to select
the operation mode. Pressing completes the operation mode
setting procedure and enters N.O./N.C. selection.
■ N.O./N.C. Selection
Select N.O. (normally open) or N.C. (normally closed).
The current selection of “no” (normally open) or “nc” (normally
closed) is displayed. Use
or
to select the desired mode.
Pressing
completes the N.O./N.C. selection procedure and
enters the chattering prevention setting.
■ Chattering Prevention
Determine the desired response time.
The current response time is dis-
played. Use
or
to select the
response time. Pressing com-
pletes the setting procedure and
enters the display color selection.
* AP-47:100, 500 ms
■ Display Color Selection
Determine the desired LED color for
numerical value display.
The current color is displayed. Use
or
to select the color.
Pressing completes the setting
procedure and returns to the
measurement mode.
* 1-d and 2-d can be selected with the AP-40RA only.
■ Display Mode Selection (AP-40RA only)
Determine the mode to display the pressure value.
The current display mode is dis-
played. Use
or
to select the
display mode. Pressing
completes the setting procedure and
returns to the measurement mode.
* Accuracy is based on the rating even when the zero-shift focus mode is
selected.
Press the button once.
Press the button once.
5.2
sm5.2
5
sm5
001
sm001
005
sm005
Press the button once.
[-1
ylnoDELdeR
[-2
DELneerg/deR
tuptuonehwDER(
)NOsnrut1
d-1
ylnoDELneerG
d-2
2DELneerg/deR
nehwneerG(
)NOsnrut1tuptuo
Press the button once.
▲
▲
▲
▲
* The setting is saved
in the EEPROM.
Press the button once.
1-F
edomgninut-otuA
3-F
tnednepedni-2
edomtuptuo
2-F
edomsiseretsyH
4-F
edomwodniW
v1
yalpsidlamroN
v01
edomsucoftfihs-oreZ
)yalpsidsemit01(
Note: The AP-40A Series is designed to display only the pressure unit
of Pa.
Contact KEYENCE for products to display other units such as mmHg,
kgf/cm
2
, bar, or PSI.