3-6 DP-V1 Service
3-27
- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (GT2) -
Executing Communication
3
64 Error state
When the sensor amplifier is
in the error state, the
corresponding bit is set.
"Types of error and error
code" (page 4-3)
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
65 Warning status
When the sensor amplifier is
in the warning state, the
corresponding bit is set.
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
66 Comparator value property
When the sensor amplifier
comparator value is invalid or
exceeding the upper or lower
limit, the corresponding bit is
set.
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
67
Comparator value over
range
When the sensor amplifier
comparator value is
exceeding the upper limit, the
corresponding bit is set.
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
68
Comparator value under
range
When the sensor amplifier
comparator value is
exceeding the lower limit, the
corresponding bit is set.
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
69 Comparator value Invalid
When the sensor amplifier
comparator value is invalid,
the corresponding bit is set.
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
70 to 77 Reserved for system
78 Output 1
When the control output of
sensor amplifier is High, the
corresponding bit is set.
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
79 Output 2
When the control output of
sensor amplifier is Low, the
corresponding bit is set.
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
80 Output 3
When the control output of
sensor amplifier is Go, the
corresponding bit is set.
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
81 Output 4
When the control output of
sensor amplifier is HH, the
corresponding bit is set.
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
82 Output 5
When the control output of
sensor amplifier is LL, the
corresponding bit is set.
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
83 to 85 Reserved for system
86 External input response 1
When the request reception
to the "External input request
1" is complete, the
corresponding bit is set.
*1
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
87 External input response 2
When the request reception
to the "External input request
2" is complete, the
corresponding bit is set.
*1
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
Index
(DEC)
Function name Description
Data