E N-R4-IM
Wiring IN1 and IN2
Wiring OUT1 to 4
Wiring the RS-422A/485 connector
Layout of RS-422A pins
Wiring the RS-422A
Use a twisted pair cable
Layout of RS-485 pins
Wiring the RS-485 (wiring to the N-410)
Processing the communication cable
1 Remove the sheath of the cable by 70 mm.
2 Cover the bare shield mesh wires and the sheath portion
with a contraction tube of about 40 mm.
3 Make stranded wires from the shield mesh wires and
prepare the required number of wires including the insulated
wires. (5 wires are required for the RS-422A and 3 wires are
required for the RS-485)
4 Remove the cover of each insulated wire by about 8 mm
from the tip.
5 Perform preliminary soldering on each wire by about 6 mm
from the tip.
The external diameter of the preliminarily soldered bare wire
must not exceed 2 mm.
Surrounding space
Install the N-R4 vertically.
When the installation direction changes, provide
adequate surrounding space so that heat does not
build up.
For ventilation, maintain a space of 50mm or more
from the top and bottom of the N-R4. As long as the
N-R4 is the only source of heat generation, the N-R4
can be installed without space on the right and left
sides.
Provide a space of 80 mm or more in front of the N-
R4 to connect the BL head.
50 mm or more on the top and bottom; no space is required on the
right and left sides
Installation precautions
When installing the N-R4, do not block the ventilation slots on the
top and bottom of the unit. Otherwise, heat builds up inside the
unit, causing product failure.
If the temperature of the N-R4 will foreseeable exceed the upper
limit of the operating temperature (50°C), take the appropriate
measures such as performing forced air cooling or ensuring
proper ventilation so that the temperature does not exceed the
upper limit of the normal operating temperature (50°C).
Symbol Description Signal direction
SD+ Data transmission + side Output
SD– Data transmission – side Output
SG Signal ground
-
RD+ Data reception + side Input
RD– Data reception – side Input
Note
The extended distance of the cable must not exceed
1.2 km.
For both the N-R4 and external equipment, set the
terminating resistance to ON.
(The terminating resistance of the N-R4 is 100 Ω.)
Symbol Description Signal direction
485+ RS-485 + side I/O
485– RS-485 – side I/O
SG Signal ground
-
Note
The extended distance of the cable must not exceed
1.2 km.
For the N-R4 at the end of the RS-485 trunk line, set
the terminating resistance to ON.
Note
Do not wire the RS-485 cable via the terminal block.
Do not install the RS-485 cable and the power line on
the same piping.
Do not branch the RS-485 line.
Use stranded copper wire having a gage of AWG12 to
30 and temperature rating of 60°C or higher.
The tightening torque is 0.56 to 0.79 N·m (5 to 7 lbf·in).
Circuit diagram
IN1, IN2
INCOM
Internal
circuit
OUT1 to 4
OUT
COM
Load
Circuit diagram
Load
Load
Load
Load
Internal circuit
External equipment
N-R4
Recommended RS-422A cable (with shield)
Manufacturer: NIHON ELECTRIC WIRE & CABLE Co., LTD
Product name:Instrumentation cable
Model: KNPEV-SB 0.75 mm
2
x 2P
N-R4
Recommended RS-485 cable (with shield)
Manufacturer: NIHON ELECTRIC WIRE & CABLE Co., LTD
Product name:Instrumentation cable
Model: KNPEV-SB (1P) 0.75 mm
2
N-R4 N-R4
Installing the N-R4
Sheath
About 70 mm
Contraction tube
About 40 mm
Shield stranded wire
Insulated wire
About 8 mm
2 mm or less
Top
Bottom
80 mm or more
from the front
80 mm
50 mm
50 mm