3-4 Command Parameter List
3-30
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-S) -
Communicating with the FD-S series
3
00
nn80
Group-4 entry
count
R-29
nn81 System reserved
nn82 Detection mode R/W - 0
0: F-1
1: F-2
2: F-3
3: A-1
4: A-2
nn83 System reserved
nn84 Response time R/W - 3
0: 0.05 s
1: 0.1 s
2: 0.5 s
3: 1.0 s
4: 2.5 s
5: 5.0 s
6: 10.0 s
7: 30.0 s
8: 60.0 s
nn85 Average display R/W - 01.0 00.0 to 10.0 (in steps of 0.5)
nn86
Time-out time for
output 2
R/W - 10 1 to 99
nn87
Integration
direction
R/W - 0
0: Increment
1: Decrement
nn88
Integrated flow
quantity unit (for
version A)
R/W
FD-SS02 4
1: 0.01 / 2: 0.1 / 3:1 / 4: 10 / 5: 100 /
6: 1000
FD-SF1(S) 4
2: 0.1 / 3: 1 / 4: 10 / 5: 100 / 6: 1000 /
7: 10000
FD-SF1(F) 4
1: 0.01 / 2: 0.1 / 3: 1 / 4: 10 / 5: 100 /
6: 1000
FD-SS2(S) 4 3: 1 / 4: 10 / 5: 100 / 6: 1000 / 7: 10000
FD-SS2(F) 4 2: 0.1 / 3: 1 / 4: 10 / 5: 100 / 6: 1000
FD-SF8(S) 4
0: 0.001 / 1: 0.01 / 2: 0.1 / 3: 1 /4: 10 /
5: 100
FD-SF8(F) 4
2: 0.1 / 3: 1 / 4: 10 / 5: 100 / 6: 1000 /
7: 10000
FD-SS20(S) 4 1: 0.01 / 2: 0.1 / 3: 1 / 4: 10 / 5: 100
FD-SS20(F) 4 3: 1 / 4: 10 / 5: 100 / 6: 1000 / 7: 10000
nn89 Zero cut level *9 R/W
FD-SS02 010.0 000.0 to 400.0
FD-SF1(S) 0050 0000 to 2000
FD-SF1(F) 010.0 000.0 to 400.0
FD-SS2(S) 0100 0000 to 4000
FD-SS2(F) 010 0000 to 400
FD-SF8(S) 00.40 00.00 to 16.00
FD-SF8(F) 0100 0000 to 4000
FD-SS20(S) 01.00 00.0 to 40.0
FD-SS20(F) 0100 0000 to 4000
nn8A
Low density zero
cut function
*10 R/W -0
0: ON
1: OFF
nn8B
Low density zero
cut level
*10 R/W - 0.50 0.01 to 2.00
nn8C System reserved
nn8D N.O./N.C. R/W - 0
Bit 0: Output 1 (1: N.C.)
Bit 1: Output 2 (1: N.C.)
Bit 2: Output 3 (1: N.C.)
nn8E Display mode R/W - 0
0: Std
1: rESo
Data
category
(HEX)
Data
number
(HEX)
Name
Description Attribute Sensor head
Default
value
Parameter range