3-3 Explicit Messaging
3-33
3
Communicating with the SK-1000 Series
- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (SK-1000) -
*7 This is 999.8 when the humidity is not acquired correctly.
*8 If a prohibited combination of functions is written, it results in "abnormal setting
(1)." For details of each function, refer to the SK-1000 Series User's Manual.
*9 The "initial reset request" motion command result is included in this item.
Regarding data category N x 10 + 1 Data No. 79 (EEPROM writing result), a "0:
writing in progress" status is maintained for 2 seconds after completion of the
final write command transmission to the nonvolatile memory (EEPROM). Writing
begins 2 seconds later, and if completed normally, the result is "1: successfully
completed".
[Example] After every-second write command transmissions, a "0: writing in
progress" status is established for 2 seconds. A "0: writing in prog-
ress" status is maintained for 2 seconds after completion of the final
write command transmission, and writing then begins 2 seconds
later, with a result of "1: successfully completed".
However, writing begins immediately follow
ing a initial reset executed in
response t
o a data category N Data No. 69 "initial reset" request. A "1: success-
fully completed" result then occurs if all parameters have been saved to the non-
volatile memory (EEPROM) approximately 3 seconds later.
- When "zero shift status save" is ON, writing begins immediately for data cat-
egory N Data No. 65 "zero shift request" and Data No. 66 "zero shift reset
request".
*10 The command reads the execution result of the "zero shift request" or "zero shift
reset request" whichever was last issued.
*11 By reading the "system parameter current state," the system parameters of the
sensor amplifier can be checked. The system parameters are comprised of the
settings of "judgment output/check output" polarity and analog output.
The "system parameter" attribute specifies the system parameters which are set
when the "system parameter set request" is executed by a
motion command.
The values t
o be read or written are specified by translating them to binaries and
using ON or OFF in each bit of the binaries.
Assume the read data is "006":
Translating "6" to a binary number gives "0110".
*12 This parameter works if "Bank switching method" is set to "button."
*13 These parameters are OFF only if data "0" is written and the wiring is configured
to turn off external input.
*14 A write control error results if data is rewritten to an expansion unit.
Bit Setting details
0
0: NPN output
1: PNP output
3, 2, 1
000: Analog output OFF
001: 0 to 5 V
010: -5 to +5 V
011: 1 to 5 V
100: 4 to 20 mA
Bit 0: NPN output
011
Bit 3, 2, 1: 1 to 5 V
0