
3-2 I/O Communication
3-12
- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (FD-MH) -
3
Communicating with the FD-MH series
IN area
n: The first device number assigned to the DL-DN1
The device assignments are the same for all 5-output modes including extended
modes.
Rewrite setting value
Sensor amplifier ID numbers 01 to 10 are assigned to bits 0 to 9, respectively.
For details of communication methods, see "Rewriting a Setting Value of a Sensor
Amplifier" (page 3-16).
3-output mode
OUT area
m: The first device number assigned to the DL-DN1
Device
(DEC)
Name
Bit 7 Bit 6 ··· Bit 1 Bit 0
Bit 15 Bit 14 ··· Bit 9 Bit 8
n+6 Integration reset response
ID08 ID07 ··· ID02 ID01
Reserved ID15 ··· ID10 ID09
n+7
Flow rate hold reset
response
ID08 ID07 ··· ID02 ID01
Reserved ID15 ··· ID10 ID09
n+8 Reserved
ID08 ID07 ··· ID02 ID01
Reserved ID15 ··· ID10 ID09
n+9
Temperature hold reset
response
ID08 ID07 ··· ID02 ID01
Reserved ID15 ··· ID10 ID09
n+10 Reserved
ID08 ID07 ··· ID02 ID01
Reser
ved ID15 ··· ID10 ID09
Device
(DEC)
Name
Bit 7 Bit 6 ... Bit 1 Bit 0
Bit 15 Bit 14 ... Bit 9 Bit 8
m+3
Request to rewrite
instantaneous flow rate
setting 1 (P1)
ID08 ID07 ... ID02 ID01
Reserved ID15 ... ID10 ID09
m+4 to 5
Instantaneous flow rate
setting 1 (P1)
Instantaneous flow rate setting 1 (P1) to be rewritten
(4-byte signed integer)
m+6
Request to rewrite
instantaneous flow rate
setting 2 (P2)
ID08 ID07 ... ID02 ID01
Reserved ID15 ... ID10 ID09
m+7 to 8
Instantaneous flow rate
setting 2 (P2)
Instantaneous flow rate setting 2 (P2) to be rewritten
(4-byte signed integer)
m+9
Request to rewrite
temperature upper limit
setting
ID08 ID07 ... ID02 ID01
Reserved ID15 ... ID10 ID09
m+10 to 11
Temperature upper limit
setting
Temperature upper limit setting to be rewritten
(4-byte signed integer)
Comentários a estes Manuais