5-1 Connecting with Sensor Amplifiers
5-3
- DeviceNet Compatible Network Unit DL-DN1 User's Manual -
5
Appendix
Different types of sensor amplifiers can be connected to a single DL-DN1. However,
restrictions described below should be observed.

Restrictions on combinations
Yes: This combination is available.
No: This combination is not available.
GT2-100 cannot be mixed with any other types of sensor amplifiers.
When GT2-7*, GT-7*A, IG, or IB is mixed, the calculation function and simultane-
ous input functions are not available.
If the connected sensor amplifiers include any of the unavailable (No) combination
above, a "Mixed connection error(0004h)" is returned to the DL-DN1.

Restrictions on the number of connectable units
Combination of GT2, GT-70A, IG, and IB series
* For combinations of seven or more units, please contact your nearest KEYENCE
office.
Combination of FD-MH and FD-S series
Limit the total number of connected units to 4.
Mixed Connection of Sensor Amplifiers
GT2-7* GT-7*A IG IB FD-MH FD-S
GT2-7* - Yes Yes Yes No No
GT-7*A Yes - Yes Yes No No
IG Yes Yes - Yes No No
IB Yes Yes Yes - No No
FD-MHNoNoNoNo - Yes
FD-S No No No No Yes -
Combination
Number of connectable units
GT2-7*
(main & expansion
units)
GT-7*A
(main & expansion
units)
IG or IB
(main & expansion
units)
Yes Yes No Max. 10 units in total
Ye s N o Ye s
Max. 6 units in total
*
However, IG or IB units must
be 4 or fewer.
No Yes Yes
Ye s Ye s Ye s