- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (SK-1000) -
3-4 Message Communication
3-38
3
Communicating with the SK-1000 Series
Group1
032BH
(811)
Bank status
Indicates the currently active bank No.
Use this attribute to check the bank No. for
which the sensor amplifier is actually
operating.
Parameter range: 0 to 3
0: Bank 0
1: Bank 1
2: Bank 2
3: Bank 3
RDINT
032CH
(812)
Timing status
Indicates the currently active timing status.
Use this attribute to check the timing status
under which the sensor amplifier is actually
operating.
Parameter range: 0 to 1
0: During Sampling
1: Not during sampling
RDINT
033DH
(813)
Temperature
*2
Indicates the current temperature.
Parameter range: -999.9 to +999.9
RDINT
033EH
(814)
Humidity
*3
Indicates the current humidity.
Parameter range: 0.0 to 100.0
RDINT
032FH
(815) to
0332H
(818)
(Reserved for system)
0333H
(819)
Abnormal
setting
*4
Indicates the abnormal setting state.
Parameter range: 0 to 1
0:Normal setting
1:Abnormal setting
RDINT
0334H
(820)
External input
status
Indicates the external input status. When the
external input cable of the sensor amplifier or
the external input of the cyclic communication
is on, the corresponding bit turns on.
This operation is enabled even when "Not
used" is selected for the function setting of
external inputs 1 through 4.
Bit0:External input 1
Bit1:External input 2
Bit2:External input 3
Bit3:External input 4
R
DWORD
0335H
(821)
EEPROM write
result
*5
Indicates the result of writing to EEPROM.
Parameter range: 0 to 2
0:Writing
1:Normal termination
2:Abnormal termination
RDINT
0336H
(822)
Zero shift/Zero
shift reset
result
*6
Indicates the result of zero shift or zero shift
reset.
Parameter range: 0 to 2
0:Executing
1:Normal termination
2:Abnormal termination
RDINT
0337H
(823)
Reset request
result
Indicates the result of reset.
Parameter range: 0 to 2
0:Executing
1:Normal termination
2:Abnormal termination
RDINT
Class
Attribute
ID
Name Description
Attribute
Data
Ty pe