Chapter 3 Use of Common Functions
3
33
3.2.2 Display scaling function [E]
This function is used to change the ratio of the displayed value relative to the
measured value (input value from the sensor head). To perform scaling, enter the
desired display value respectively for two desired correction points.
Example
To display the original display value changing from "1" to "5" as a value changing
from "0" to "10"
1. Press the
key for at least 2 seconds.
The sensor enters the common function selection mode.
2. Press the
key to select function "E".
Check that "E" is flashing.
3. Press the
key to enter the display scaling function setting state.
4. Press the
key to select the input method. After the selection, press the
key to save the input method setting.
Pressing the
key changes the input method number.
Select "0" or "1" and follow the procedure described below according to the
selected input method.
15
1
5
1
0
10
Before scaling After scaling
Display Display
Original display
5
Original display
Setting
Point 1
Original display (input value) : 1.000
Changed display (display value) : 0.000
Point 2
Original display (input value) : 5.000
Changed display (display value) : 10.000
SET
CALL
HIGH TIM
GO
LOW
FUNC
UTILITY
MODE
CALIB
Using input value from
sensor head for setting
Using operation key
input for setting