2.4 Instruction Details
1
2
3-103
Chapter 2 Instructions
Example
Coding
Description
When input relay 0000 is ON:
0500 turns ON as soon as 0001 turns ON.
0501 turns ON as soon as 0002 turns ON.
0502 turns ON as soon as 0003 turns ON.
The MPS instruction is used at the start of an output branch.
The MRD instruction is used to connect an output branch.
The MPP instruction is used at the end of an output branch.
When the KV IncrediWare (DOS)/LADDER BUILDER for KV programming
support software is used, the MPS, MRD, and MPP instructions are automatically
converted into mnemonics and entered in the ladder diagram.
Note 1: Limit the number of MPS instructions to 8 or less in a circuit.
Note 2: An MPS instruction must have a corresponding MPP instruction. This
means that the same number of MPS and MPP instructions must be used in a
program. An MPS or MPP instruction without a corresponding MPP or MPS instruc-
tion results in a logic error.
Operands
Key operation
MPS: Push
MRD: Read
MPP: Pop
Stores current input and arithmetic flag
status.
Reads input and arithmetic flag status
stored with PUSH.
Reads and clears input and arithmetic flag
status stored with PUSH.
Line No. Instruction Operand
0000 LD 0000
0001 MPS
0002 AND 0001
0003 OUT 0500
0004 MRD
0005 AND 0002
0006 OUT 0501
0007 MPP
0008 AND 0003
0009 OUT 0502
MPS
C
MRD
D
MPP
ch
0000
0501
0500
0001
0002
0003
0502
MRD
MPP
MPS
MPS
C
MRD
D
MPP
ch
ENT
R-SRCH
:
:
:
MPS / MRD / MPP
KVNKA Chap 02_4bP.p65 08.3.11, 0:00 PM103