2.4 Instruction Details
1
2
3-121
Chapter 2 Instructions
ITVL
■ A/D data measurement
Turns ON output relay 0500 when the analog input from the KL-4AD to DM1600
(range: 1 to 5 V) exceeds +3 V. Turns ON output relay 0501 when the input is below
+2 V. Writes the average into DM0100.
Refer to the "KL-4AD/KL-2AD User’s Manual" for data memory settings for the KL-
4AD.
Coding
2008
2008
2008
2008
2003
0001
0002
1000
#01600
LDA
DM0000
STA
#02000
LDA
DM0001
STA
#01000
LDA
DM0002
STA
#00100
LDA
DM0003
STA
PLS
DM0000
PAUSE
1000
RES
ITVL
1001
1003 DM0100
STA
DM0007
LDA
0500
0501
Writes average into DM0100 every 100 measurement.
Measures contents of DM1600.
Sets max. setting value to +3 V (2000).
Sets min. setting value to +2 V (1000).
Sets number of averaging measurements to 100.
Pauses measurement when input relay 0001 turns ON.
Resets measurement when input relay 0002 turns ON.
0500 turns ON when measured value exceeds max. setting value.
0501 turns ON when measured value is below min. value.
Line No. Instruction Operand Line No. Instruction Operand
0000 LD 2008 0014 CON
0001 LDA #01600 0015 STA DM0003
0002 CON 0016 LD 2003
0003 STA DM0000 0017 LD 0001
0004 LD 2008 0018 LD 0002
0005 LDA #02000 0019 ITVL DM0000 1000
0006 CON 0020 LD 1000
0007 STA DM0001 0021 OUT 0500
0008 LD 2008 0022 LD 1001
0009 LDA #01000 0023 OUT 0501
0010 CON 0024 LD 1003
0011 STA DM0002 0025 LDA DM0007
0012 LD 2008 0026 STA DM0100
0013 LDA #00100
KVNKA Chap 02_4bP.p65 08.3.11, 0:00 PM121