3-5 Overview of PROFIBUS DP Communication
3-18
- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (IG) -
Executing Communication
3
Device maps
Monitor mode
In the monitor mode, the following functions can be performed.
Reading the control output to the sensor amplifiers: "Parameterization" (page 3-8)
External input request to the sensor amplifiers: "Parameterization" (page 3-8)
Reading the comparator value: "Parameterization" (page 3-8)
Reading the error status: "Parameterization" (page 3-8)
DL-PD1 (Slot 0)
Input
Octet Bit Function name Description Value
0
0 Reserved for system - -
1 Reserved for system - -
2 Comparator value property Stores the comparator value status.
0: Normal
1: Disabled status
----”, “FFFF”, or “-FFFF
3 Reserved for system - -
4 Reserved for system - -
5 Sensor ready
It is output when PROFIBUS DP
communication is established.
0: Starting
1: Ready
6 Reserved for system - -
7 Error status
Stores the error status of the sensor
amplifiers.
"Types of error and error code"
(page 4-3)
0: No error occurred.
1: Error occurred.
1
0 External input response 1
Stores the external input response to
the sensor amplifier.
0: No input
1: Input reception
1 External input response 2
Stores the external input response to
the sensor amplifier.
0: No input
1: Input reception
2 External input response 3
Stores the external input response to
the sensor amplifier.
0: No input
1: Input reception
3 External input response 4
Stores the external input response to
the sensor amplifier.
0: No input
1: Input reception
4 External input response 5
Stores the external input response to
the sensor amplifier.
0: No input
1: Input reception
5 Reserved for system - -
6 Reserved for system - -
7 Reserved for system - -