Keyence DL-PD1 Manual do Utilizador Página 53

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 52
3-6 DP-V1 Service
3-31
- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (IG) -
Executing Communication
3
36
Judgment output / Edge
check output
*2 DINT R
Bit0:
HIGH judgment output
0: OFF, 1: ON
Bit1: LOW judgment output
0: OFF, 1: ON
Bit2: GO judgment output
0: OFF, 1: ON
Bit3: Edge check
0: OFF, 1: ON
37
Current value (P.V. value)
*3
*4
DINT R -99.999 to +99.999
38
Raw value (R.V. Value)
*3
*4
DINT R -99.999 to +99.999
39
Peak-hold value in hold mode
*3
*4
*5
DINT R -99.999 to +99.999
40
Bottom-hold value in hold
mode
DINT R -99.999 to +99.999
41
Calculation value (CALC
Value)
*3
*4
*6
DINT R -99.999 to +99.999
42 Analog output value *7 DINT R
Analog voltage output:
-5.000 to +5.000
Analog current output:
+04.00 to +20.00
43 to 44 Reserved for system
45 Number of edges *8 DINT R 0 to 99
46 Optical axis alignment state DINT R
0: Optical axis alignment NG
(optical axis alignment
indicator OFF)
1: Optical axis alignment OK
(optical axis alignment
indicator ON)
47 to 50 Reserved for system
51 Abnormal setting *9 DINT R
0: Normal setting
1: Abnormal setting
52 Reserved for system
53 EEPROM writing result *10 DINT R
0: Currently executing
1: Successfully completed
2: Writing failed
54
Zero shift/Zero shift reset
executing result
*11 DINT R
0: Currently executing
1: Successfully completed
2: Unexecutable
55 Reset request result DINT R
0: Currently executing
1: Successfully completed
2: Unexecutable
56
System parameter current
state
*12 DINT R 0 to 15
57 Reserved for system
Index
(DEC)
Function name
Description
Data
type
Attribute
Default
value
Value
Vista de página 52