3-18
IB-E
3
Basic Operations
3-7
Zero Shift Function (Shifting the
Internal Measurement Value (R.V.))
The internal measurement value (R.V.) is shifted (offset) to an arbitrary shift target value.
The judgment value (P.V.) is shifted (offset) as well.
The following two methods can be used.
Press the [ZERO SHIFT] button (within 1 second).
Set the external input (zero shift input) to ON for 2 ms or more.*
* When the zero shift input is set for the external input 1 (pink wire), the zero shift is
enabled when the input is triggered.
"10. External Input" (page 4-29)
1
Press the / button several times on the main screen. To display the
shift target value on the sub display (lower level).
"Sub Display (Lower Level)" (page 3-4)
2
Press the / button to set the shift target value.
"1. Measurement Mode" (page 4-8)
3
Press the / button to return the sub display to the original screen.
Setting the Shift Target Value
Item Measurement mode Setting range Default value
Shift target
value
% mode -999.99 to 999.99
0.00
Dimension mode -99.999 to 99.999
0.000
GO
HOLD CALC
CHECK

LASER
BANK
0
1
2
3
HI
LO
R.V.
ANALOG
HI SHIFT
ZERO SHIFT
TIMING
LO
ALIGNMENT

Shift target value
[
SHIFT]
ON