7.6 Display Interface Mode Programming
KV-300 Series Only
KV-300
KV-10/80
Chapter 7 KV-L2 Serial Interface Module
1-286
7
Command format
An instruction word is specified with uppercase alphabetical characters.
An underscore (_) represents a space.
Response format (When the command is executed normally, the response
includes the end code "00".)
Note 1: Temporary memory addresses can be changed by bit.
Note 2: An underscore (_) in the instruction word represents a space. Include the
underscore in the instruction word when transmitting the command.
Note 3: The station no., ch. to change, and bit to change are indicated in decimal;
the end code, in hexadecimal.
Set/reset multiple channels (FK)
This command sets or resets the ON/OFF status of the specified I/O relay, internal
utility relay, temporary data memory address, timer, counter, or high-speed counter
comparator by channel.
Command format
* An instruction word is specified with uppercase alphabetical characters. An
underscore (_) represents a space.
@
KR FCS
C
R
Station No.
nn
Device
xxxx
Ch. no. to
change nnnn
Bit to change
nn
Header code
00 to 15
(in decimal)
Terminator
Station No.
nn
@
KR FCS
C
R
End code
nn
Header code
Terminator
@
FK FCS
C
R
Station No.
nn
Device
xxxx
Channel to
change
nnnn
Data to force-set/-reset
mmmmmmmmmmmmmmmm
Header
code
00 to 15
(in decimal)
Terminator
"m" represents a bit of data
(total: 16 bits)
Device Ch. No. to change Bit to change Data
CIO_ 0000 to 0179 00 to 15 I/O relay, internal utility relay
HR_ _ 0000 to 0031 00 to 15 Temporary memory address
AR_ _ 0000 to 0179 00 to 15 I/O relay, internal utility relay
TIM_ 0000 to 0249 00 Timer
CNT_ 0000 to 0249 00 Counter
CNT_ 0250 to 0253 00 High-speed counter comparator CTC
Device Ch. No. to change Bit to change Data
CIO_ 0000 to 0179 00 to 15 I/O relay, internal utility relay
HR_ _ 0000 to 0031 00 to 15 Temporary memory address
AR_ _ 0000 to 0179 00 to 15 I/O relay, internal utility relay
TIM_ 0000 to 0249 00 Timer
CNT_ 0000 to 0249 00 Counter
CNT_ 0250 to 0253 00 High-speed counter comparator CTC
KVHKA Chap 07_5to10.p65 08.3.11, 11:18 AM286